Abstract

This paper evaluated the performance of the building integrated solar thermal shading (BISTS) system on building energy consumption and daylight levels through energy and daylighting modeling and simulations. A medium office reference building in Los Angeles defined by the DOE was used in the case studies. The horizontal BISTS louvers on the south windows and vertical BISTS louvers on the east and west windows were modeled and simulated. The final BISTS configuration was achieved by considering the balance between primary energy savings and daylight provision. The results revealed that 1) the BISTS system could effectively improve the daylight condition for a single perimeter room by increasing the useful daylight level and reducing the excessive level. 2) The savings for the building energy consumption were not significant. The final design with the BISTS layouts on three façades could result in 5.3% of total primary energy saving. 3) 90° of slat angle should be avoided for both the horizontal and vertical BISTS louvers. Smaller angles – between 0° and 60° – are preferred.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.