Abstract

In this first part of a two-part paper, a new active magnetic regenerator (AMR) laboratory apparatus is presented and evaluated. The setup is composed of a nested Halbach cylinder magnetic circuit (maximum magnetic flux density of 1.69 T) assembled in phase with a double effect displacer that provides the cold and hot blows to the regenerator. A single packed-bed regenerator with 195.5 g of gadolinium spheres is used in a discontinuous (i.e., reciprocating) cycle. The system performance is evaluated in terms of characteristic curves (i.e., cooling capacity as a function of temperature span), coefficient of performance and second-law efficiency as a function of the utilization factor and operating frequency. Maximum values of COP have been identified for a given temperature span. The maximum values of second-law efficiency were obtained at system temperature spans between 15 and 20 K.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.