Abstract

This study deals with the performance of the ejector-vapour compression cycle assisted by solar. The effect of operating conditions on the combined cycle performance is examined. Also, a comparison of the system performance with environment friendly refrigerants (R134a, R600, R123, R141b, R142b, R152a, R290, and R245fa) is made. This performance is calculated using an empirical correlation. Thermodynamic properties of functioning fluids are obtained with package REFPROP 8. Using the typical meteorological year file containing the weather data of the city of Tunis, the system performance is computed for three collector types. The theoretical results show that the R290 offers the highest coefficient of performance, COP=3.75, for generator temperature TB = 78°C, condenser temperature Tc = 30°C and the intercooler temperature Te = 15°C.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.