Abstract

Simulation of a 100 kW ammonia-water compression–absorption system has been carried out for water chilling application by incorporating detailed heat and mass transfer calculations in the absorber and desorber of the system. Warner's technique has been used for the convergence of iterations. The effect of relative solution heat exchanger area on the COP, cooling capacity, absorber heat load and effectiveness of solution heat exchanger has been studied. With increase in the relative solution heat exchanger area from 17 to 50%, COP increases initially, becomes maximum at 39% and then decreases. However, capacity of the system decreases considerably as a result of increase in relative solution heat exchanger area. Due to pressure drop in the solution heat exchanger on weak solution side, pumping power increased by 30% but COP decreased by only 0.92%. The performance of this system has been compared with that of a conventional vapor compression type chiller. ► Simulation of a 100 kW ammonia-water compression–absorption system for cooling application. ► Actual heat and mass transfer calculations in the absorber and desorber. ► The effect of relative solution heat exchanger area and various pressure drops on the performance. ► An optimum SHX area exists at which COP of the system becomes maximum. ► Comparison of compression–absorption system with vapor compression system.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.