Abstract

Performance of ejector-flash tank-absorption cooling system working with NH3/H2O is still subject for further enhancement. The aim of this study is to optimize the utilization of the internal heat recovery of the system. Two modifications are considered, namely, a new arrangement of solution streamlines between the absorber and generator and adding a refrigerant heat exchanger (RHE) between the condenser and evaporator. Energy balance analysis is performed to compare the COP enhancement of the proposed cycle before and after modification. The COP of the proposed cycle after modification showed a significant COP enhancement about 12.2%. The COP increment with the new arrangement of the solution streamlines and adding RHE are 8% and 4.2% respectively. The results show that the cooling capacity increment of the proposed cycle with added RHE is 4.85%. Moreover, the results showed that the proposed cycle significantly reduced the generator thermal load and increased slightly the evaporator thermal load (i.e., cooling effect) compare to the cycle before modification.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.