Abstract

This paper presents dynamic performance comparison of a fuzzy logic-based proportional, integral, and derivative controller (FPID) with different membership functions such as triangular, trapezoidal, and Gaussian for load frequency control (LFC) in an interconnected two-area thermal power system. The parameters of controller are optimized by using spider monkey optimization (SMO) algorithm. The superiority of the proposed algorithm is established by comparing the results with popularly used algorithms like particle swarm optimization (PSO) and teaching–learning-based optimization (TLBO). Initially, the linearized model of the system is considered with reheat turbine; then, the study is extended by imposing nonlinearity such as generation rate constraints (GRC) and governor dead band (GDB). The result comparison is analyzed using various time domain specifications like peak undershoot, peak overshoot, and settling time of different area frequencies and tie-line power deviation between them applying a step load perturbation (SLP) of 1%.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.