Abstract

The physical and electrical properties of crosslinked polyethylene (XLPE) and ethylene propylene rubber (EPR) are compared in the context of their use in transmission class cables. Results indicate that the 138-kV XLPE cable has AC withstand/breakdown strength at least 25% higher than the 150-kV EPR cable. The XLPE cable exhibits about 70% higher impulse strength than the EPR cable. The loss factor of the XLPE cable is at least 20 times lower than that of EPR cable. Thus with XLPE cables, the yearly energy savings can be on the order of 15 MWh/cct. km for a 69-kV system, 52 MWh/cct. km for a 138-kV system and 127 MHh/cct. km for a 230-kV system.< <ETX xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">&gt;</ETX>

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.