Abstract
The objective of this study is to investigate the performance characteristics of an injection CO2 (carbon dioxide) HPWH (heat pump water heater) at various operating conditions. In the standard and standby heat loss test conditions, the performance of a two-stage CO2 HPWH adopting a SCVI (sub-cooler vapor injection HPWH) cycle was measured and analyzed by varying the compressor frequency, the water flow rate, and the injection ratio at various outdoor temperatures. In the standard tests at the outdoor temperature of −15 °C, the COP (coefficient of performance) of the optimized SCVI HPWH was 7.6% higher than that of the non-injection HPWH. During the standby loss tests at the water flow rate of 200 kg h−1, the COP of the optimized SCVI HPWH was 7.1% higher than that of the non-injection HPWH.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.