Abstract

In this study, the performance of a small-capacity directly cooled refrigerator was evaluated by using the mixture of R290 and R600a with mass fraction of 55:45 as an alternative to R134a. The compressor displacement volume of the alternative system with R290/R600a (55/45) was modified from that of the original system with R134a to match the refrigeration capacity. Both systems with R290/R600a (55/45) and R134a were tested, and then optimized by varying the refrigerant charge and capillary tube length under experimental conditions for both the pull-down test and the power consumption test. The refrigerant charge of the optimized R290/R600a system was approximately 50% of that of the optimized R134a system. The capillary tube lengths for each evaporator in the optimized R290/R600a system were 500 mm longer than those in the optimized R134a system. The power consumption of the optimized R134a system was 12.3% higher than that of the optimized R290/R600a system. The cooling speed of the optimized R290/R600a (55/45) system at the in-case setting temperature of −15 °C was improved by 28.8% over that of the optimized R134a system.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.