Abstract

In this study energy, exergy and exergoeconomic analysis of the Afyon geothermal district heating system (AGDHS) in Afyon, Turkey is performed through thermodynamic performances and thermo-economic assessments. In the analysis, actual system data are used to assess the district heating system performance, energy and exergy efficiencies, exergy losses and loss cost rates. Energy and exergy losses throughout the AGDHS are quantified and illustrated in the flow diagram. The energy and exergy efficiencies of the overall system are found to be 37.59% and 47.54%, respectively. The largest exergy loss occurs in the heat exchangers with 14.59% and then in the reinjection wells with 14.09%. Besides, thermo-economic evaluations of the AGDHS are given in table. Energy and exergy loss rates for the AGDHS are estimated to be 5.36 kW/$ and 0.2 kW/$, respectively.