Abstract

In order to solve the problem of poor regeneration performance of the solar solution dehumidification air conditioning regeneration system under high temperature and high humidity weather conditions. In this paper, a novel vacuum membrane distillation (VMD) solution regeneration method was proposed for a solution desiccant air conditioning system, and a theoretical study of this novel regenerator is performed. Through the analysis of heat and mass transfer, the mathematical model of VMD regeneration is established, and the mathematical model is verified by experiments. The results indicated that VMD regenerator not only could increase the regenerate rate but also could exhibit higher energy utilization efficiency. At the same concentration, the VMD regenerator has a higher regeneration performance, and the regeneration rate is 1.6–2.4 times that of the internal heat type regenerator, and the 4.5–6 times that of the adiabatic regenerator.