Abstract

We present a novel pulsed flow control method (PFM) using a two-position valve to regulate the capacity of radiant slab systems. Under PFM, the on-time duration of the valve is short (compared to all prior work, e.g. 4-minute), and fixed, while the off-time varies. We present a novel, open-source, finite difference model that assesses three-dimensional transient slab heat transfer, accounting for the transient heat storage of the pipe fluid. Sensitivity analysis results indicate the dominant factors influencing energy performance of the PFM are: on-time duration; pipe diameter; and spacing. We experimentally validated both the new control strategy and model in full-scale laboratory experiments. Compared with previous intermittent control strategies (with on-time durations over 30 min), at 50% part load the PFM reduces 27% required water flow rate and increases supply to return water temperature differential. Compared with the variable temperature control method, at 50% part load the PFM reduces 24% required water flow rate. The energy performance of PFM is comparable to that of a conventional variable flow rate control. However, it has more accurate capacity control, achieves a more uniform surface temperature distribution, and reduces initial investment by substituting two-position for modulating valves, thus showing promise for engineering applications.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.