Abstract

<p class="Abstract">The conventional three-phase alternating current (AC) to direct current (DC) converter can be modified using two isolated-gate bipolar transistor (IGBT) as by-pass switches connected to tapping points on the secondary side of the transformer. This scheme yields a reduction in both harmonic contents and reactive volt-ampere absorption. This modified converter possibly eliminates the need for an on-load tap-changer on the converter transformer. The modified AC/DC converter is fully analyzed and implemented under balanced conditions using MATLAB-Simulink. The expressions of the output DC voltage are derived for different cases. The supply current harmonic contents, the reactive power absorption and the power factor have been compared for three schemes; the conventional bridge, the modified bridge using one by-pass IGBT valve and the modified bridge with two by-pass IGBT valves. </p>

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.