Abstract

Data centers (DCs) require continuous cooling throughout the year and produce a large amount of low-grade waste heat. Free cooling and waste heat recovery techniques are promising approaches to reduce DC energy consumption. Although previous studies have explored diverse waste heat utilization strategies, there is a significant gap in combining waste heat recovery with lake water cooling in DCs. Therefore, this study proposed a system integrating lake water cooling with waste heat recovery for DCs. To evaluate the energy-saving performance of the suggested system, the influence of waste heat recovery locations and volumes has been investigated. An analysis of the improvement in system parameters is also conducted. The study’s findings highlight that targeted recovery of waste heat from sources like chilled water or air in server rooms can significantly reduce the cooling energy demand of the system. The results show that recovering heat from the return air of IT equipment can yield a remarkable power usage effectiveness (PUE) and coefficient of performance (COP) of 1.19 and 10.17, and the energy consumption of the cooling system is reduced to 10.06%. Moreover, the outcomes reveal the potential for substantial energy savings of up to 26.05% within the proposed system by setting the chilled water and air supply temperatures to 16 and 20 °C, respectively.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.