Abstract

The potential implementation of hybrid photovoltaic (PV)/diesel energy system in western region of Saudi Arabia is analyzed in this paper. The solar radiation intensity considered in this study is in the range of 4.15–7.17 kWh/m2/day. The HOMER software is used to perform the technical and economical analysis of the system. Three different system configurations, namely, stand-alone diesel system, and hybrid PV/diesel system with and without battery storage element, will be evaluated and discussed. The analysis will be addressed to the impact of PV penetration and battery storage on energy production, cost of energy, number of operational hours of diesel generators, fuel savings, and reduction of carbon emission for the given configurations. The simulation results indicate that the energy cost of the hybrid PV/diesel/battery system with 15% PV penetration, battery storage of 186.96 MWh, and energy demand of 32,962 MWh/day is $0.117/kWh.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.