Abstract

In this study, the performance of the horizontal type ground source heat pump cooling system in the summer was analyzed for cooling the testing area with a size of 9x8x2.8m in Diyarbakir province with a warm climate. Energy and exergy analysis was applied to the system and system units by examining the results obtained in the summer in the evaluated system. The monthly and seasonal mean values of the data in the summer (01.06.2018 / 30.08.2018 ) were taken for 11 node points determined in the installed system. In the energy analysis performed with the results obtained, it was calculated that the energy loss in the system was 2.499kW and the energy efficiency 76.86%. For the system units, the unit operating with the lowest energy efficiency was determined as the compressor. According to exergy analysis applied to the system, it was calculated that the exergy loss of the system was 2.150 kW and the second law efficiency was 20.70%. The compressor was also determined as the unit with the highest exergy loss in the system. Compressor should be prioritized for improvement studies to be planned according to both energy and exergy analysis results. The COP value of the system was found to be 4.05, and it was determined that the system, the use of which was examined in the summer, could be used for Diyarbakir province.

Highlights

  • Due to gradual reduction of energy resources and the rapid increase in energy prices nowadays, efficient use of energy has become a necessity

  • In the summer (01 June 2018 - 31 August 2018), the electricity consumption of the scroll type compressor used in the horizontal type ground source heat pump cooling system was affected in direct proportion to external air temperature, it was determined that scroll type compressor started to operate more at high air temperatures

  • In the analyses performed in this context, it was determined that system COP values were affected in direct proportion to external air temperatures

Read more

Summary

Research Article

The performance of the horizontal type ground source heat pump cooling system in the summer was analyzed for cooling the testing area with a size of 9x8x2.8m in Diyarbakır province with a warm climate. Energy and exergy analysis was applied to the system and system units by examining the results obtained in the summer in the evaluated system. In the energy analysis performed with the results obtained, it was calculated that the energy loss in the system was 2.499kW and the energy efficiency 76.86%. According to exergy analysis applied to the system, it was calculated that the exergy loss of the system was 2.150 kW and the second law efficiency was 20.70%. The compressor was determined as the unit with the highest exergy loss in the system. Compressor should be prioritized for improvement studies to be planned according to both energy and exergy analysis results. The COP value of the system was found to be 4.05, and it was determined that the system, the use of which was examined in the summer, could be used for Diyarbakır province

Introduction
Material And Method
PE ṁ
Ėxproduct Ė xfuel
Node Number
June July August
Condenser Evaporator Throttling Valve
Conclusions