Abstract
The objective of the current study is to assess the technical performance of Aquifer Thermal Energy Storage (ATES) based on the monitoring data from 73 Dutch ATES systems. With a total abstraction of 30.4 GWh heat and 31.8 GWh cold per year, the average annual amount of supplied thermal energy was measured as 932.8 MWh. The data analysis revealed only small thermal imbalances and small temperature losses during the storage period. The abstraction temperatures are around 10 and 15 °C during summer and winter, respectively. However, the temperature difference between the abstraction and injection wells is 3–4 K smaller compared to the optimal design value. This indicates insufficient interaction between the energy system and the subsurface by an inadequate charging of the aquifer. In addition, the amount of stored and abstracted thermal energy is approximately 50% lower than the capacities licensed by the authorities. This results in an unsustainable utilization of the subsurface. Even though ATES technology proved its enormous potential to significantly reduce CO2 emissions, the operation still can be optimized. This applies in particular to an adequate planning and maintenance of the building energy system and a more efficient use of the available subsurface space.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.