Abstract

This paper deals with the protection against earth faults in distribution networks with unearthed or compensated neutral. A transient-based protection system is proposed and assessed through electromagnetic transient program (EMTP) simulations. The fault detection algorithm is based on the estimation of the angle between the zero-sequence voltage and current phasors. The estimation is carried out at the dominant transient frequency of the network response within the first milliseconds after the fault. The implementation of an improved filter and a zero-padding process allows for the identification of high resistance faults with a relatively low sampling frequency. An operation zone is proposed and assessed, also for unbalanced or mixed bare and cable line networks. The performances of the protection system are evaluated for a distribution network in both the cases of unearthed and compensated neutral through a Monte Carlo method that considers the fault resistance, incidence angle and fault location variations as random variables in the EMTP simulations.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.