Abstract
Reducing peak power demand in a building can reduce electricity expenses for the building owner and contribute to the efficiency and reliability of the electrical power grid. For the building owner, reduced expenses come from the reduction or elimination of peak power charges on electricity bills. For the power system operator, reducing peak power demand leads to a more predictable load profile and reduces stress on the electric grid system. We present a computationally inexpensive, dynamic, and retrofit-deployable control strategy to effect peak load reduction and load shaping. The effectiveness of the control strategy is examined in a simulation with 80 air-conditioning units and 40 refrigeration units. The results show that a peak demand reduction of 60 kW can be achieved relative to peak demand in a typical set point–based approach. The proposed strategy was deployed in a gymnasium building with four rooftop HVAC units, where it showed over 15% peak demand (kW) reduction savings while maintaining or lowering energy consumption (in kilowatt-hours) relative to the set point–based thermostat controls.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.