Abstract
Radiant chilled ceilings (RCC) are known as cost-effective cooling methods. In this study, phase change material (PCM) was used to improve RCC, and its thermal analysis under the Tabuk climate in Saudi Arabia was discussed. By creating an air gap inside the roof, RCC integrated PCM. With the creation of an air gap and proper PCM placement, heat exchange from the ceiling declined by 57.6% in an annual analysis and 22.6% from April to the end of October. Acceptable PCM performance is due to phase changes during the day. For PCM to be effective in the daytime, it must be frozen overnight. Three methods were used to accelerate PCM freezing: a nanofluid-filled ground heat exchanger, cool ambient airflow and chilled water. The share of the first method in accelerating PCM solidification was 78.6%, and the percentage of the second and third methods was 16.5%. Although the performance of the cool airflow was not suitable for PCM freezing in the PCM embedded radiant chilled ceiling when the cool airflow enters the interior as ventilation, it can reduce power demand by 26.1% in April and by 25.3% in October, but it was not helpful in July and August.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.