Abstract

Principal component analysis (PCA) and Fisher discriminant analysis (FDA) are presented in this paper to detect and diagnose the single sensor fault with fixed bias occurring in variable air volume systems. Based on the energy balance and the flow-pressure balance, both related to physical models of the systems, two PCA models are built to detect the occurrence of abnormalities in the systems. In addition, FDA, a linear dimensionality reduction technique, is developed to diagnose the fault source. Through the Fisher transformation, different faulty operation data classes can be optimally separated by maximizing the scatter between classes while minimizing the scatter within classes. Then the faulty sensor can be isolated through comparing Mahalanobis distances of the candidate sensors.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.