Abstract

The aim of this study was to verify the efficiency of removal of microorganisms in effluents of a Wastewater Treatment Plant (WWTP) comprising an association of a UASB reactor followed by three submerged aerated biofilters (BAF) and one tertiary filter. The WWTP designed to treat domestic wastewater from a population of 1,000 inhabitants showed high removal efficiency for organic matter and suspended solids. Helminth eggs were also efficiently removed from the tertiary effluent and were found in the sludge from the UASB reactor; however, removal of bacteria in this system was very low. To enhance the efficiency of the system, the effluent from tertiary filters was submitted to UV disinfection in a real scale reactor. Our results showed that UV irradiation was very effective at lowering the concentrations of E. coli, thermotolerant coliforms and coliphages to acceptable levels for agricultural reuse. Salmonella spp. and helminth eggs were seeded into the tertiary effluent before passing through the UV reactor. Salmonella was not found in the final effluent, but helminth eggs were not completely inactivated by UV irradiation and viable eggs were detected after 28 d of incubation.