Abstract

This paper presents a passivity-based control (PBC) for a type 2 static synchronous compensator (STATCOM) based on an Euler-Lagrange model. The proposed method is designed based on a Lyapunov function by considering dissipation to improve transient performance. An additional nonlinear damping term is designed to regulate the capacitor voltage. It is guaranteed that the equilibrium point of the system is locally exponentially stable in the operating range. The performance of the proposed method is validated via a 100 Mvar STATCOM system connected to the 345-kV grid system in SimPowerSystems, MATLAB/Siumlink. To compare with the input-output feedback linearization method, the proposed control method has improved convergence and reduction of oscillations of the active current and DC voltage, as shown in simulation results. Lastly, it shows that the proposed method is robust to model mismatches as the variation of the grid voltage and the degradation of the capacitance.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.