Abstract

As attention has focused on indoor air quality, it has become important to obtain basic information on the effects of heating, ventilating, and air-conditioning system operating parameters on office aerosols. In addition, it is important to know the particle size distributions (PSDs) in a typical office environment in order to address mitigation strategies. Therefore, this study was undertaken to evaluate the effect of percent outdoor air supplied and occupation level on the PSDs and mass concentrations for a typical office building. The outdoor, return, and supply air streams, as well as hallway air, were sampled using measuring equipment covering particle diameters from below 0.1 to above 3.5 μm. The mass concentrations, when the building was occupled, increased by a factor of approximately 2 when return air was recycled over ventilating with maximum outdoor air. The concentrations when unoccupied were at least as low using minimum outdoor air as those when occupied using maximum outdoor air. As expecte...

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.