Abstract

Because of the large capital value of power transformers and their critical role in the electricity network, there is an increasing need for non-intrusive diagnostic and monitoring tools to assess their internal condition. The UHF technique is being applied increasingly to monitor partial discharges (PD) in power transformers and has been shown to be much more sensitive than acoustic techniques when the signal path passes through solid insulation. Field trials were performed on five power transformers ranging in size from 18 to 1000 MVA and in voltage from 25 to 400 kV. The results of PD tests on power transformers provide sufficient evidence to justify making provision for UHF sensors on new transformers to facilitate their monitoring when required during the service lifetime.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.