Abstract
This paper deals with the analysis of partial discharge (PD) occurrences based on leakage current (LC) pulses distribution under different level of contamination. In this work, laboratory based contamination performance tests are conducted on four units of glass insulator string stacked in I-position. Results show that PD can be characterized (according to their occurrence with respect to the AC supply) as follows: corona discharge occurring dominantly in lightly contaminated insulators, surface discharge occurring dominantly in medium contaminated insulators and finally internal discharge occurring dominantly in heavily contaminated insulators. The ability to distinguish the type of PDs from the LC waveform could be used to monitor and predict the condition of the insulator. The outcome can be incorporated in a conditioning monitoring system.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.