Abstract

High reliability, independence from environmental conditions, and the compact design of gas-insulated systems will lead to a wide application in future high voltage direct current (HVDC) transmission systems. Reliable operation of these assets can be ensured by applying meaningful and robust partial discharge diagnosis during development tests, acceptance tests, or operation. Therefore, the discharge behavior must be well understood. This paper aims to contribute to this understanding by investigating the partial discharge behavior of a distorted weakly inhomogeneous electrode arrangement in sulfur hexafluoride (SF6) and synthetic air under high DC voltage stress. In order to get a better understanding, the partial discharge current is measured under the variation of the insulation gas pressure, the gas type, the electric field strength, and the voltage polarity. Derived from this, a classification of the different discharge types is performed. As a result, four different discharge types can be categorized depending on the experimental parameters: discharge impulses, discharge impulses with superimposed pulseless discharges, discharge impulses with superimposed pulseless discharges, and subsequent smaller discharges and pulseless discharges. Concluding suggestions for partial discharge measurements under DC voltage stress are given: recommendations for the necessary measurement time, the applied voltage and polarity, and useful measurement techniques.

Highlights

  • Gas-insulated systems (GIS) have been the state-of-the-art in high voltage alternating current (HVAC) transmission grids since the 1960s [1]

  • Current measurements are a promising technique for the investigation of the partial discharge behavior in gas-insulated systems under DC voltage stress

  • The evaluation of the measured electron and ion current increased the understanding of discharge processes at one common partial discharge (PD) source in gas-insulated systems, a protrusion

Read more

Summary

Introduction

Gas-insulated systems (GIS) have been the state-of-the-art in high voltage alternating current (HVAC) transmission grids since the 1960s [1] These systems have major advantages compared to air-insulated systems (AIS) like their space-saving design, their independence from environmental conditions, and their higher reliability. These advantages are beneficial for high voltage direct current (HVDC) transmission systems as well. Due to the growing importance of renewable energy sources and their integration into the existing power grid, longer transmission lines have to be built. This is economically feasible only by using HVDC technologies. Gas-insulated HVDC systems are a space-saving solution for HVDC substations

Objectives
Methods
Results
Discussion
Conclusion
Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call