Abstract

The purpose of this work is to determine the values of electrical parameters of synchronous and induction machines to validate electrical interactions between an induction generator and a synchronous generator. The generators are connected in two ways: (i) isolated from the common bus and (ii) parallel to the common bus in steady state, subject to nonlinear load. They are old and refurbished machines; thus, the parametric regression methodology is used to determine the electrical parameter values. After the computational model validation, analyses are performed by various system configurations to confirm the repowering and to analyze the system harmonic current flow. The results obtained comparing the computer simulation and experimental tests prove that the validated model represents the real system. With an experimentally validated computational model, it is possible to verify the occurrence of system repowering and the increased value of harmonic distortions in the induction generator terminals, acting as a preferential path for harmonic currents.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call