Abstract

Detailed simulations have been performed for a single zone building to calculate the maximum heating and cooling loads as well as specific annual energy consumption for a single zone building. Numerical results have been used to derive parametric equations as a function of the thickness of insulation as well as the surface to volume ratio ( A/ V) taking into account the effect of increasing height as well as increasing length and width. For un-insulated building, the energy consumption increases steeply with increasing height, whereas for an insulated building, the energy consumption decreases slightly. For increasing lengths and widths, the change in energy consumption is a mild positive slope. The optimum thickness of the insulation obtained in the paper corresponds to the recommended U-values of roof and the walls in the building code of India, U being the total heat transfer coefficient.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.