Abstract

Precisely assessing plasma parameters holds paramount importance in investigating the arc extinguishing mechanism of semi-sealed splitter plate DC circuit breakers, refining the configuration of splitter plates, and optimizing the overall structural design of circuit breakers. Based on the principle of the Langmuir probe, a double probe diagnostic method is proposed to investigate the air arc plasma in the opening process of a DC circuit breaker. The diagnostic circuit of the probes is designed, and three sets of double probes are arranged to trace the evolution of the plasma density during the opening process. The research reveals that the plasma center density, measured by the diagnostic system during the opening process of the DC circuit breaker, is about 1022 m−3–1023 m−3. This density is compared with the diagnostic results obtained by other methods, confirming the accuracy of the Langmuir double probe for plasma measurements in the DC circuit breaker. The study also revealed an exponential decay behavior of electron density along the radial direction of the arc. A mathematical model was employed to describe this phenomenon, establishing a relationship between the distribution of electron density and arc current.