Abstract

Arc interruption of high voltage direct current (HVDC) circuit breakers (CBs) is one of the main challenging factors for using HVDC grids. To evaluate the arc interrupting capability in HVDC CBs, black box arc models are used to represent the nonlinear arc conductance depending on Cassie and Mayr dynamic arc equations. Extensive simulation studies are carried out to investigate the effect of controlled and uncontrolled parameters on the CB arcing time. A real line represents a part of 500 kV electrical connection systems between Egypt and the Kingdom of Saudi Arabia is simulated to be a faulty load. It is found that the arcing time of the HVDC CB can be reduced by increasing the value of cooling power coefficient ( p ) and decreasing the value of arc time constant ( τ ). It is also deduced that the arcing time is reduced by the increase of the commutation capacitance value ( C ) and decreasing the commutation inductance ( L ) value and vice versa. Moreover, it is concluded that the arcing time is greatly affected by the fault location and the fault arc resistance (R f ) according to fault conditions.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.