Abstract

AbstractThe lumped element network model has been proven to be an efficient tool for the interpretation of transformer Frequency Response Analysis. However, it is challenging to obtain parameters of the model if transformer design information is unavailable. In such a case, optimisation algorithms can be used for gray‐box model parameter estimation. A methodology is developed by the authors to establish a transformer network model without winding design data, and instead, end‐to‐end open circuit Frequency Response and other terminal test results are utilised; and Genetic Algorithm is applied to approximate the unknown parameters of the model. The modelling approach developed is independent of the unit number of the network model and therefore guarantees the accuracy of optimisation. Furthermore, it can deal with transformers with a complicated winding structure such as interleaved disc type winding. Two single windings, helical and interleaved disc type, and a single‐phase 144/13 kV 60 MVA transformer are used to demonstrate the method. FRA spectra produced by the best estimated gray‐box model and the corresponding white‐box model are compared. The main features in amplitude and phase spectra are well matched, with low values of Relative Standard Deviation, for both single windings and transformer. Estimated electrical parameters show a high consistency with reference values, which are calculated based on winding design data. This validates the methodology and gives confidence to apply grey‐box modelling for FRA interpretation.