Transmission line parameters are essential inputs to various power system analysis programs and applications such as protective relaying algorithms, and precision of line parameters is thus significant in ensuring the analysis accuracy and algorithm reliability. This paper proposes methods for estimating positive sequence parameters of a series compensated transmission line. The methods are based on distributed parameter line model and utilize voltages and currents from both terminals of the line during normal operations. In particular, based on nonlinear estimation theory, an optimal estimator is designed for deriving positive sequence line parameters. The algorithm is capable of detecting and identifying bad measurement data, and thus improving the estimation accuracy. The proposed method is independent of the operation status of the compensation device.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.