Abstract

The dielectric recovery characteristic of high voltage circuit breaker (HVCB) is determined by the interaction of the electric field and the flow field in interrupting course, the calculation field of electric and gas flow are different, and the initial computation and boundary conditions are also different. For obtaining the corresponding data to numerically solve the dielectric recovery characteristic of the CB, the parallel coupled strategy is proposed and employed for computing the coupled electric and flow field. Moreover, in the pre-processing, the sub-region meshing method is used and the elements in some region with rapid variation are densified. The feasibility and practicability of the proposed method with high efficiency has been verified by the demonstration example. And the distribution of the flow field, the electric field and the curve of the dielectric recovery characteristic in the whole interrupting course have been obtained. The location of the minimum of the dielectric recovery characteristic during the course of interrupting is traced. Furthermore, the coupled strategy in parallel can effectively calculate the dielectric recovery strength. And discussions about the acquired results are presented

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call