Abstract

Abstract :The aerodynamic performance of double inlet sirocco fan is strongly dependent upon the design factors of impeller and scroll. In this paper, the change of scroll size was adopted to investigate the aerodynamic performances of double inlet sirocco fan and indoor PAC. Especially, a scroll expansion angle and a cut-off clearance ratio were considered to change the scroll size. In addition, the installation depth between double inlet sirocco fan and indoor PAC was considered. As a result, the total pressure efficiency of double inlet sirocco fan shows about 62%∼73% according to the change of scroll expansion angles. Moreover, the flowrate performance of indoor PAC is the best at the condition of a scroll expansion angle of 8°, an installation depth of 15 mm and a cut-off clearance ratio of 8%. Key Words :Aerodynamic Performance, Cut-off Clearance Ratio, Double Inlet Sirocco Fan, Sirocco Impeller, Package Air-Conditioner, Scroll, Scroll Expansion Angle *†김장권(교신저자) : 군산대학교 동력기계시스템공학과E-mail : flowkim@kunsan.ac.kr, Tel : 063-469-1848** 오석형 : 군산대학교 기계공학부*†Jang-Kweon Kim(corresponding author) : Department of Power System Engineering, Kunsan National University.E-mail : flowkim@kunsan.ac.kr, Tel : 063-469-1848** Seok-Hyung Oh : School of Mechanical Engineering, Kunsan National University.