Abstract
The Nordic Power System is undergoing significant transformation and development in the coming years. A driving factor for this is the increased dependency on renewable energy sources and high voltage direct current transmission (HVDC). Various stability challenges due to the dynamics of reactive power - voltage (Q-V) balancing and active power - frequency (P-f) balancing seep into the system with such rise of non-synchronous generation (NSG). This paper investigates the projected impact of NSGs on the P-f dynamic performance of Nordic power system in 2030. As NSGs are systems with low inertia, power discrepancies lead to larger oscillations, higher Rate of Change of Frequency (RoCoF) and bigger maximum frequency deviation (MFD) values. To address these issues, Emulated Inertia (EI) control for wind turbines and Synthetic Inertia (SI) control for VSC-HVDC links are proposed in this paper. The simulation is carried out using DIgSILENT PowerFactory 2022 SP1 simulation software. The results obtained confirm the Effectiveness of the proposed EI and SI methods to enhance frequency response and mitigate deviations.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.