Abstract

In the current source photovoltaic grid-connected system, to prevent the DC-link inductor from incurring an opening circuit fault, it is necessary to include the overlap time in the switching signals. However, current error and serious harmonic distortion in the inverter-side and grid-side currents are generated, which will cause additional losses and reduce the power quality of the grid, so it is important to compensate for the current error caused by the overlap time. In this paper, the relationship between the nonlinear current errors caused by the overlap time and the AC-side voltage is analyzed. Then, the mathematical expression of the low-order harmonics with losses caused by the overlap time is derived. On this basis, a current error compensation method with a discrete filter of AC-side voltage is proposed. Finally, a simulation and experiment are carried out to verify the correctness and effectiveness of the theoretical analysis and compensation scheme presented in this paper. With an overlap time of 3 μs, the THD of the grid-side current decreases from 5.93% to 1.59% after compensation.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.