Abstract

Overheating of flexible tinned copper connectors has been observed at a number of power stations. These connectors are used to connect the generator to outgoing busbars and transformers thus serving to counter the effects of vibration and thermal expansion forces. It is shown that the main cause for the observed overheating is a result of a combined action of the high initial contact resistance, fretting, stress relaxation, differential thermal expansion and the formation of intermetallics at the copper-tin interfaces.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.