Abstract

Addressing the overheating fault detection and alarming of insulated busways in buildings, a system based on sensing volatile gases generated by the thermal degradation of the busduct insulation layer was proposed. By monitoring the concentration of volatile gases in the environment, the overheating fault of the busducts can be found early. The thermal degradation process of the busway insulating layer is analyzed, and the pyrolysis characteristic gas at low temperature is studied. The experimental platform has been built, by which the relation between the concentration of volatile gases and temperature of the insulated layer has been studied. By testing, the concentration of volatile organic compounds (VOCs) is proposed as the basis for judging the overheating fault in the alarming system. With the collected samples for training and testing, the AdaBoost classifier is used to identify the overheating fault. Finally, the design of the overheating fault alarming system is given.