Abstract
This paper presents an online fault-tolerant control strategy. By correcting the faulty measurements with a final correcting factor, the strategy covers five steps: fault detection, construction of correcting alternatives, performance forecasting, alternatives outranking, and fault correction. System energy, indoor air quality, human thermal comfort, and control efficiency are considered as a whole to evaluate the operating performance. Taking the supply air temperature sensor faults as testing examples, the strategy is tested in a virtual air conditioning system and simulated on TRNSYS platform. The testing results show that a large fault correcting factor is obtained in the first hour, an adjusting phase presents in the next several hours, and the correction factor keeps unchanged finally. High level of calculating accuracy is required for the performance prediction model. Also, for the outranking evaluation model, the thresholds and weight coefficients should be assigned appropriately to meet the requirements of building functions and/or owners.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.