Abstract

Biodiesel has great potential to be applied in a variety of combustion engines, such as boiler. The excess air control in the combustion process plays an important role to produce an ideal combustion performance. The changes in the physical properties of the fuel due to the use of palm biodiesel or its blends affect the amount of required air to the combustion chamber. This study was conducted in a package type fire tube boiler with a design pressure of 3 bars and heat capacity of 60,000 kCal/hour. Palm biodiesel blends were set as boiler fuel with composition of 10%, 20%, 30% and 50% in diesel oil. Fan damper scale is part of the burner system that in charge to regulate the air flow into the combustion chamber. The fan damper scale was set in the range of 4.0-4.9. For higher blends of biodiesel, the fan damper was optimum in lower scale (4.0 or less). More biodiesel in blends, less combustion air was needed to enter. Hence, the excess air of palm biodiesel combustion in fire tube boiler was in range of 57-67%.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.