Abstract

This paper focuses on a scenario with a high amount of renewable generators (DGs) in the distribution grid; a local grid operator (DSO) utilizes reactive power provision by the DGs, to improve the reactive power balance at the connection points to the transmission grid. At the same time, the transmission grid operator (TSO) aims to optimize his voltage, by computing reactive power setpoints for the DSO. This is a decentralized optimization problem, where two optimizers (DSO and TSO) balance the reactive power flow between their grid areas. No optimizer has detailed information about the neighbouring grid area and uses a very simple equivalent model for it. In case these equivalents are updated iteratively, we find that both optimizers mostly converge within only a few iterations for a realistic Danish grid topology. However, it is also found that the accuracy of the result highly depends on the built-in component models that each optimizer uses, within its own grid area.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.