Abstract

The current design and operation of air-cooled condensers can cause a significant decrease in chiller performance under part load conditions. This paper demonstrates optimal condenser fan control to improve the coefficient of performance (COP) of air-cooled chillers. This control involves identifying the optimum set point of condensing temperature with the optimized power relationships of the compressors and condenser fans and enhancing the airflow and heat transfer area of the condensers. An example application of this control for an air-cooled centrifugal chiller indicated that the COP could increase by 11.4–237.2%, depending on the operating conditions. Such the increase of the COP results in a reduction of up to 14.1 kWh/m 2, or 27.3% in the annual electricity consumption per unit A/C floor area of chillers, given that the chillers serve an office building requiring an annual cooling energy per unit A/C floor area of 173.3 kWh/m 2. The simulation results of this study will give HVAC engineers a better understanding of how to optimize the design and operation of air-cooled chillers.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.