Abstract

Spray cooling of a hot surface was investigated to ascertain the effect of nozzle-to-surface distance on critical heat flux (CHF). Full cone sprays of Fluorinert FC-72 and FC-87 were used to cool a 12.7 × 12.7 mm2 surface. A theoretical model was constructed that accurately predicts the spray’s volumetric flux (liquid volume per unit area per unit time) distribution across the heater surface. Several experimental spray sampling techniques were devised to validate this model. The impact of volumetric flux distribution on CHF was investigated experimentally. By measuring CHF for the same nozzle flow rate at different nozzle-to-surface distances, it was determined CHF can be maximized when the spray is configured such that the spray impact area just inscribes the square surface of the heater. Using this optimum configuration, CHF data were measured over broad ranges of flow rate and subcooling, resulting in a new correlation for spray cooling of small surfaces.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.