Abstract

Thermal performance of vortex tube is noticeably influenced by its geometrical and operational parameters. In this study effect of various geometrical (L/D ratio: 15, 16, 17, 18; exit valve angle; 300, 450, 600, 750, 900; cold end orifice diameter: 5, 6 and 7mm, tube divergence angle: 00, 20, 30, 40) and operational parameters (inlet pressure: 2 to 6 bars) on the performance of vortex tube have been investigated experimentally. Multiple Attribute Decision Making (MADM) techniques are applied to determine the optimum combination of the vortex tube. Performance of vortex tube was analysed with optimum temperature difference on cold end, COP for cooling. The MADM (Multiple Attribute Decision Making) methods, namely WSM (Weighted Sum Method), WPM (Weighted Power Method), TOPSIS (Technique for Order Preference by Similarity to Ideal Solution) and AHP (Analytical Hierarchy Process) are applied. Experimental best performing combinations are obtained for Length to Diameter ratios 15, 16, 17 with exit valve angle as 450,750 and 900 at orifice diameter 5mm for inlet pressure of 5 and 6 bar pressure. Best COP, efficiency and cold end temperature difference are 0.245, 40.6% and 38.3K respectively for the combination of 15 L/D, 450 valve angle, 5mm orifice diameter and 2 bar pressure by MADM techniques.