Abstract

In the paper, the optimization of the coagulation process for Kaolin and humic acid removal using polymeric aluminum ferric sulfate (PAFS) was studied. In order to obtain the maximum turbidity and humic acid removal efficiency of Kaolin and humic acid simulated wastewater, the optimum coagulation conditions was investigated with the factors of mixing speed and time. Furthermore, mixing speed and time including parameters affecting the coagulation performance such as rapid mixing speed, rapid mixing time, slow mixing speed and slow mixing time using single factor and orthogonal array L9 (34) analysis were examined. The results showed that the optimum single factor of mixing speed and time indicated rapid mixing speed of 350 rpm, rapid mixing time of 1.0 min, slow mixing speed of 60 rpm and slow mixing time of 20 min. Then the orthogonal optimization experiment of mixing speed and time indicated maximum HA removal efficiency was 97.5% at rapid mixing speed of 350 rpm, rapid mixing time of 1.25 min, slow mixing speed of 60 rpm, and slow mixing time of 20 min.