In this paper, optimization of the influence of the process parameters of ground source heat pump (GSHP) with the double U tube heat exchanger for space heating applications was performed. The coefficient of performance (COPsys) in GSHP system was investigated during experimental measurements with various process parameters; space air inlet/outlet temperatures (Ti,sa and To,sa) and soil inlet/outlet temperatures (Ti,wa and To,wa). Taguchi method performed for obtained the optimum process conditions on the COPsys in GSHP system. Taguchi experimental design considered as L16 orthogonal array. The most influence of process parameter on the COPsys in GSHP system was evaluated by using analysis of variance (ANOVA) and signal/noise (S/N) ratio. The optimum process parameter was determined as A4B1C1D1 for COPsys in GSHP with ANOVA analysis. The optimum levels were computed as Ti,sa at Level 1 (32 °C), the To,sa at Level 2 (17°C), the Ti,wa at Level 2 (6°C) and and the To,wa at Level 1 (9°C). The most significant parameter on the COPsys for space heating applications of GSHP system were found as Ti,sa and To,sa with 48.4 %..

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.