Abstract

Optimization of guide vane positions in bended inflow of mechanical draft wet-cooling tower Optimization of vane positions in a mechanical draft wet-cooling tower is presented in this paper. The originally installed, equally spaced, vanes produced non-uniform air velocity distribution reducing the performance of the fill of the cooling tower. A 2D CFD model of the tower has been created. The model has then been used to determine the objective function in the optimization procedure. The selected objective function was the standard deviation of the velocity of air entering the fill. The Goal Driven Optimization tools of the ANSYSWorkbench 2.0 have been used for the optimization and the ANSYS Fluent 13.0 as a flow solver. The optimization allowed reduction of the objective function and producing a more uniform air flow.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.