Abstract

Taking an office building in Qingdao as the research object, the optimal operation of the solar coupled ground source heat pumps system using frequency conversion technology at load side and source side is studied, The possibility of variable flow operation of air conditioning water system and the control strategy of variable frequency pumps are analyzed. The selection of the equipmets is completed based on the hourly load of the office building through the year. Based on the dynamic simulation software, the simulation model of solar coupled ground source heat pumps is established. The results show that the energy saving rate of variable frequency pumps is 53.18%, the energy saving rate of the heat pumps unit is-12.91%, the total energy saving rate of the system is 9.00%, and the annual performance coefficient of the system is 3.86, and the overall energy saving effect is remarkable.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.