n present study, the removal of Ca2+ from cooling tower water using Amberlite IR120 and Amberjet 1200 was optimized using the response surface methodology (RSM). The effect of operational parameters such as contact time (min), pH, dosage (mL), concentration (mg/L) and temperature (K) were investigated using a central composite design. The regeneration of the Amberlite IR120 and Amberjet were also studied. The study aimed to apply RSM to investigate and optimize the ion exchange operating parameters. Furthermore, the second-order empirical model was developed and correlated sufficiently to the ion exchange experimental data. The optimal ion exchange operating conditions for Amberlite IR120 and Amberjet 1200 were found to be: contact time was 120 min, dosage of 150 mL, the initial pH level of 2, a concentration of 4,00 mg/L and temperature of 343 K. Regeneration of Amberlite IR120 and Amberjet 1200 using 0.5 M NaCl stripping solution initially showed an increase in % Ca2+ and Mg2+ removal, then a decrease in subsequent cycles.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.